Protect yourself against future threats.
-----BEGIN PGP SIGNED MESSAGE----- Hash: SHA256 =========================================================================== AUSCERT External Security Bulletin Redistribution ESB-2021.0941 Advisory (icsa-21-075-03) Hitachi ABB Power Grids AFS Series 17 March 2021 =========================================================================== AusCERT Security Bulletin Summary --------------------------------- Product: Hitachi ABB Power Grids AFS Series Publisher: ICS-CERT Operating System: Network Appliance Impact/Access: Denial of Service -- Remote/Unauthenticated Resolution: Patch/Upgrade CVE Names: CVE-2020-9307 Original Bulletin: https://us-cert.cisa.gov/ics/advisories/icsa-21-075-03 - --------------------------BEGIN INCLUDED TEXT-------------------- ICS Advisory (ICSA-21-075-03) Hitachi ABB Power Grids AFS Series Original release date: March 16, 2021 Legal Notice All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/ . 1. EXECUTIVE SUMMARY o CVSS v3 6.5 o ATTENTION: Low skill level to exploit o Vendor: Hitachi ABB Power Grids o Equipment: AFS Series o Vulnerability: Infinite Loop 2. RISK EVALUATION Successful exploitation of this vulnerability could cause a denial-of-service condition on one of the ports in a HSR ring. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Hitachi ABB Power Grids reports the vulnerability affects the following products in the AFS Series: o AFS660/AFS665 Version 7.0.07, including the following variants: AFS660-SR AFS665-SR 3.2 VULNERABILITY OVERVIEW 3.2.1 INFINITE LOOP CWE-835 A crafted HSR frame can cause a denial-of-service condition on one of the ports in a HSR ring. CVE-2020-9307 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is ( AV:A/AC:L/PR:N/UI:N/S:U/ C:N/I:N/A:H ). 3.3 BACKGROUND o CRITICAL INFRASTRUCTURE SECTORS: Energy o COUNTRIES/AREAS DEPLOYED: Worldwide o COMPANY HEADQUARTERS LOCATION: Switzerland 3.4 RESEARCHER Hitachi ABB Power Grids reported this vulnerability to CISA. 4. MITIGATIONS Hitachi ABB Power Grids has published an advisory for AFS Series and advises users to update products with available updates. The update removes the vulnerability by modifying the way the switch processes HSR frames. For additional information and support, contact a product provider or Hitachi ABB Power Grids service organization. For contact information, see Hitachi ABB Power Grids contact-centers . CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should: o Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet . o Locate control system networks and remote devices behind firewalls, and isolate them from the business network. o When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.cisa.gov . Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies . Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies . Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents. No known public exploits specifically target this vulnerability. This vulnerability is not exploitable remotely. For any questions related to this report, please contact the CISA at: Email: CISAservicedesk@cisa.dhs.gov Toll Free: 1-888-282-0870 CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product. - --------------------------END INCLUDED TEXT-------------------- You have received this e-mail bulletin as a result of your organisation's registration with AusCERT. The mailing list you are subscribed to is maintained within your organisation, so if you do not wish to continue receiving these bulletins you should contact your local IT manager. If you do not know who that is, please send an email to auscert@auscert.org.au and we will forward your request to the appropriate person. NOTE: Third Party Rights This security bulletin is provided as a service to AusCERT's members. As AusCERT did not write the document quoted above, AusCERT has had no control over its content. The decision to follow or act on information or advice contained in this security bulletin is the responsibility of each user or organisation, and should be considered in accordance with your organisation's site policies and procedures. AusCERT takes no responsibility for consequences which may arise from following or acting on information or advice contained in this security bulletin. NOTE: This is only the original release of the security bulletin. It may not be updated when updates to the original are made. If downloading at a later date, it is recommended that the bulletin is retrieved directly from the author's website to ensure that the information is still current. Contact information for the authors of the original document is included in the Security Bulletin above. If you have any questions or need further information, please contact them directly. Previous advisories and external security bulletins can be retrieved from: https://www.auscert.org.au/bulletins/ =========================================================================== Australian Computer Emergency Response Team The University of Queensland Brisbane Qld 4072 Internet Email: auscert@auscert.org.au Facsimile: (07) 3365 7031 Telephone: (07) 3365 4417 (International: +61 7 3365 4417) AusCERT personnel answer during Queensland business hours which are GMT+10:00 (AEST). On call after hours for member emergencies only. =========================================================================== -----BEGIN PGP SIGNATURE----- Comment: http://www.auscert.org.au/render.html?it=1967 iQIVAwUBYFGBduNLKJtyKPYoAQgIHA//Xbc7kE76S6uZmjduvY78Is+UlvrQ0zdP iYrxRsKYOJJsnS46eEDl9Dh8i/LMHeD9zvsaEgKaYmF1nN11nyX9u5tOaJKbpPcc aiA1L4+hxlcJZNUSlSFUxeSmpJGDuly2TDZ3eqNorPB2CzekJiQmTZGo2EbAc4p+ GQJdil066fa1GDTCSs5oYKxON6/ro2qDxgKV+LLbCDlmfZj/qj2FdTIq7ui9iAoH dmH18M7EQRU4CyS+Kpfy5Dr7TLxEMy+gFfYVPg7c9hemzXpC4Bcw+nTLY+ov4RAA 60ptnr9njA5kBU8wIxl2+1YJhzCJVNJQgj4uFN4r9jLyy4qgn0pTGxmy41tCIC0h xG4V6hYNFTLfGgv4Cfgn4nsSBTuXo0RNiZrwzj7puxXW67d+gn85A4Fy/a5Qa8Bv 5aH9ALCoYBTtvq0kNeb5DnpTYxuxtXnoZHc14+2KU+EaY5uBps3kDACDB5X7u8Y9 adXN9wLtGvVH+tamUxhwqPDPeBYoIgaCmgbebk0tUZyoew6vXo4FMvDSMZCR8RaM e4Fm0mAAmHZ27H9UH8rSC8CBptxEOgpo6/5PhzqPQTubixqTlQgXdyOBJdAD6kN/ 8EuG8XkrzszAXTNOUttnGhAel5xCmAw8GQDB5uxzJf5ELSNuTW9mp8BJO5CJTdU3 oatLruF+PuQ= =WXIC -----END PGP SIGNATURE-----