Protect yourself against future threats.
-----BEGIN PGP SIGNED MESSAGE----- Hash: SHA1 =========================================================================== AUSCERT External Security Bulletin Redistribution ESB-2014.1452 Advisory (ICSA-14-238-01) CG Automation Improper Input Validation 27 August 2014 =========================================================================== AusCERT Security Bulletin Summary --------------------------------- Product: ePAQ-9410 Substation Gateway Publisher: US-CERT Operating System: Network Appliance Impact/Access: Denial of Service -- Remote/Unauthenticated Resolution: Patch/Upgrade CVE Names: CVE-2014-0762 CVE-2014-0761 Original Bulletin: https://ics-cert.us-cert.gov//advisories/ICSA-14-238-01 - --------------------------BEGIN INCLUDED TEXT-------------------- Advisory (ICSA-14-238-01) CG Automation Improper Input Validation Original release date: August 26, 2014 Legal Notice All information products included in http://ics-cert.us-cert.gov are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see http://www.us-cert.gov/tlp/. OVERVIEW Researchers Adam Crain of Automatak and Chris Sistrunk of Mandiant have identified an improper input validation vulnerability in the CG Automation ePAQ-9410 Substation Gateway DNP3 protocol components. CG Automation has produced an updated software that mitigates this vulnerability. CG Automation has tested the updated software to validate that it resolves the vulnerability. This vulnerability could be exploited remotely. AFFECTED PRODUCTS The following CG Automation products are affected: ePAQ-9410 Substation Gateway, all versions. IMPACT Successful exploitation of this vulnerability could allow an attacker to affect the availability of the DNP3 Master Server software. Impact to individual organizations depends on many factors that are unique to each organization. NCCIC/ICS-CERT recommends that organizations evaluate the impact of this vulnerability based on their operational environment, architecture, and product implementation. BACKGROUND CG Automation is a US-based company with other CG offices in several other countries around the world, including the US, UK, Netherlands, Italy, India, Germany, France, Czech Republic, China, and Australia. The affected product, ePAQ-9410 Substation Gateway, is a gateway used in electric utility. According to CG Automation, ePAQ-9410 Substation Gateway is deployed across the Energy Sector. CG Automation estimates that this product is used primarily in the United States and Europe with a small percentage in Asia and South America. VULNERABILITY CHARACTERIZATION VULNERABILITY OVERVIEW IMPROPER INPUT VALIDATION-IP-BASED [a] The CG Automation Software DNP3 driver, used in the ePAQ-9410 Substation Gateway products, does not validate input correctly. An attacker could cause the software to go into an infinite loop by sending a specifically crafted TCP packet, causing the process to crash. The following scoring is for IP-connected devices. CVE-2014-0761 [b] has been assigned to this vulnerability. A CVSS v2 base score of 7.1 has been assigned; the CVSS vector string is (AV:N/AC:M/Au:N/C:N/I:N/A:C).[c] IMPROPER INPUT VALIDATION-SERIAL-BASED [d] The CG Automation Software DNP3 driver, used in the ePAQ-9410 Substation Gateway products, does not validate input correctly. An attacker could cause the software to go into an infinite loop, causing the process to crash. The system must be restarted manually to clear the condition. The following scoring is for serial-connected devices. CVE-2014-0762 [e] has been assigned to this vulnerability. A CVSS v2 base score of 4.7 has been assigned; the CVSS vector string is (AV:L/AC:M/Au:N/C:N/I:N/A:C).[f] VULNERABILITY DETAILS EXPLOITABILITY The IP-based vulnerability could be exploited remotely. The serial-based vulnerability is not remotely exploitable. Local access to the serial-based outstation is required. EXISTENCE OF EXPLOIT No known public exploits specifically target this vulnerability. DIFFICULTY An attacker with a moderate skill could craft a TCP packet that would be able to exploit the vulnerability for an IP-based device. An attacker with a high skill could exploit the serial-based vulnerability because physical access to the device or some amount of social engineering is required. MITIGATION CG Automation has fixed this vulnerability with updated software. Users may obtain the updated software by downloading from this web address: http://mail.cgautomationusa.com/login.aspx ICS-CERT encourages asset owners to take additional defensive measures to protect against this and other cybersecurity risks. Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet. Locate control system networks and remote devices behind firewalls, and isolate them from the business network. When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices. ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT Web page at: http://ics-cert.us-cert.gov/content/recommended-practices. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. Additional mitigation guidance and recommended practices are publicly available in the ICSCERT Technical Information Paper, ICS-TIP-12-146-01BTargeted Cyber Intrusion Mitigation Strategies, that is available for download from the ICS-CERT Web site (http://ics-cert.us-cert.gov/). Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents. a. CWE-20: Improper Input Validation, http://cwe.mitre.org/data/definitions/20.html, web site last accessed August 26, 2014. b. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-0761, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory. c. CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:M/Au:N/C:N/I:N/A:C, web site last accessed August 26, 2014. d. CWE-20: Improper Input Validation, http://cwe.mitre.org/data/definitions/20.html, web site last accessed August 26, 2014. e. NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2014-0762, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory. f. CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:L/AC:M/Au:N/C:N/I:N/A:C, web site last accessed August 26, 2014. Contact Information For any questions related to this report, please contact ICS-CERT at: Email: ics-cert@hq.dhs.gov Toll Free: 1-877-776-7585 International Callers: (208) 526-0900 For industrial control systems security information and incident reporting: http://ics-cert.us-cert.gov ICS-CERT continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product. - --------------------------END INCLUDED TEXT-------------------- You have received this e-mail bulletin as a result of your organisation's registration with AusCERT. The mailing list you are subscribed to is maintained within your organisation, so if you do not wish to continue receiving these bulletins you should contact your local IT manager. If you do not know who that is, please send an email to auscert@auscert.org.au and we will forward your request to the appropriate person. NOTE: Third Party Rights This security bulletin is provided as a service to AusCERT's members. As AusCERT did not write the document quoted above, AusCERT has had no control over its content. The decision to follow or act on information or advice contained in this security bulletin is the responsibility of each user or organisation, and should be considered in accordance with your organisation's site policies and procedures. AusCERT takes no responsibility for consequences which may arise from following or acting on information or advice contained in this security bulletin. NOTE: This is only the original release of the security bulletin. It may not be updated when updates to the original are made. If downloading at a later date, it is recommended that the bulletin is retrieved directly from the author's website to ensure that the information is still current. Contact information for the authors of the original document is included in the Security Bulletin above. If you have any questions or need further information, please contact them directly. Previous advisories and external security bulletins can be retrieved from: http://www.auscert.org.au/render.html?cid=1980 =========================================================================== Australian Computer Emergency Response Team The University of Queensland Brisbane Qld 4072 Internet Email: auscert@auscert.org.au Facsimile: (07) 3365 7031 Telephone: (07) 3365 4417 (International: +61 7 3365 4417) AusCERT personnel answer during Queensland business hours which are GMT+10:00 (AEST). On call after hours for member emergencies only. =========================================================================== -----BEGIN PGP SIGNATURE----- Comment: http://www.auscert.org.au/render.html?it=1967 iQIVAwUBU/1mSRLndAQH1ShLAQKL1g/+Op4S6uakZJKLMmQMRINr/wP9PQGx8RaA JIv5pVu6NaPwmX/szdR23mVTPybMw2rn7RWW+iAzoA4uqylx2RETEay00defQJRE R1hMjo/agG2Kb1mrEqelUQ3j2lm6syGUAEFyKsqOE5mrrrzz4mkxIi0xkyb4tiOV LA5d+M+s0UYfwD2PwmcGltCzrpjYrFhxIKiiTqpzMhsEmQGoZg5eDDDOHG33zgCQ QUaa+05PKc0NGQ06tDX5iRUa49dLDUBvxdlOqYNBR2PMNJ+9KZkUrT8xnaEjACkz gaIt14W6quayYK48EJ0Xz9YZUfbEhGirTnfi8sAou/ytIn6sF5rRTfP31nfTN9p5 0/zDLGx8MiLB9Z/CsSyF3M5HLRQSwextJWJ9kAyOjT9lZt6p17MFqyckeQcvnPLL CnG5Odi8F7asLBg8OFRilakLHvKI8rJQbF+7Lr6npTSseNDyL7e7tQ8915kehJZy toLq/WrRtvBVDaWeXoaPR1+REKjT+IKW8zxcGtuNWYLmey5tatt0p++kzq84pq2i FRNHQoWhgaQE9wjUg27inLZHeMnpQOBj+al4yDgXmClEgY1w8wWBi+jybWpbUGa1 V4ESc/LQHbjWlc2uuXaxSBWOxl+opFtXVBiwMXFCo4YD6RKdQFHUMOIlhtbP3Dl2 94fSSsgVD/Y= =Tqqj -----END PGP SIGNATURE-----