Date: 20 March 2013
Click here for printable version
Click here for PGP verifiable version
-----BEGIN PGP SIGNED MESSAGE-----
Hash: SHA1
===========================================================================
AUSCERT Security Bulletin
ASB-2013.0043
SSA-714398: Vulnerabilities in WinCC 7.0 SP3 Update 1
20 March 2013
===========================================================================
AusCERT Security Bulletin Summary
---------------------------------
Product: Siemens WinCC & SIMATIC PCS7
Operating System: Windows Server 2003
Windows Server 2008
Windows Server 2008 R2
Windows 7
Windows XP
Impact/Access: Execute Arbitrary Code/Commands -- Remote with User Interaction
Denial of Service -- Remote with User Interaction
Access Confidential Data -- Existing Account
Unauthorised Access -- Existing Account
Reduced Security -- Existing Account
Resolution: Patch/Upgrade
Member content until: Friday, April 19 2013
OVERVIEW
Multiple vulnerabilities have been identified in Siemens SIMATIC WinCC
version 7.0 SP3 Update 1 and below. SIMATIC PCS 7 Web Server is also
affected by these vulnerabilities. [1]
IMPACT
The vendor has provided the following description regarding these
vulnerabilities:
"Vulnerability 1
WebNavigator passwords stored in the SQL database are only obfuscated.
CVSS Base Score 2.7
CVSS Temporal Score 2.1
CVSS Overall Score 2.1
(AV:A/AC:L/Au:S/C:P/I:N/A:N/E:POC/RL:OF/RC:C)
Vulnerability 2
Users with legitimate, non-privileged access to WinCCs MS SQL database
can retrieve
obfuscated user passwords for WebNavigator. For doing this, access to
the system is needed either locally or from the adjacent network and
the users account must have adequate permissions.
CVSS Base Score 2.7
CVSS Temporal Score 2.1
CVSS Overall Score 2.1
(AV:A/AC:L/Au:S/C:P/I:N/A:N/E:POC/RL:OF/RC:C)
Vulnerability 3
Authenticated users may manipulate the URL in the web browser to
access the file system of the web server. With this vulnerability they
may read all the files that are readable in the web server context.
CVSS Base Score 4.0
CVSS Temporal Score 3.1
CVSS Overall Score 3.1
(AV:N/AC:L/Au:S/C:P/I:N/A:N/E:POC/RL:OF/RC:C)
Vulnerability 4
An ActiveX control RegReader which is installed in the users web
browser is susceptible to a buffer overflow. An attacker might trick a
victim into visiting a malicious web site which calls this ActiveX
control, triggers the overflow and take over the victims PC.
CVSS Base Score 6.8
CVSS Temporal Score 5.3
CVSS Overall Score 5.3
(AV:N/AC:M/Au:N/C:P/I:P/A:P/E:POC/RL:OF/RC:C)
Vulnerability 5
By opening a manipulated project file, sensitive data can be
transmitted over the network or a DoS condition can be provoked.
CVSS Base Score 5.8
CVSS Temporal Score 4.5
CVSS Overall Score 4.5
(AV:N/AC:M/Au:N/C:P/I:N/A:P/E:POC/RL:OF/RC:C)
Vulnerability 6
By sending a specially crafted packet to a dynamically assigned port,
an attacker can generate a DoS condition against WinCC.
CVSS Base Score 6.1
CVSS Temporal Score 5.0
CVSS Overall Score 5.0
(AV:A/AC:L/Au:N/C:N/I:N/A:C/E:F/RL:OF/RC:C)" [1]
MITIGATION
The vendor recommends updating to WinCC 7.2. [1]
REFERENCES
[1] SSA-714398: Vulnerabilities in WinCC 7.0 SP3 Update 1
http://www.siemens.com/corporate-technology/pool/de/forschungsfelder/siemens_security_advisory_ssa-714398.pdf
AusCERT has made every effort to ensure that the information contained
in this document is accurate. However, the decision to use the information
described is the responsibility of each user or organisation. The decision to
follow or act on information or advice contained in this security bulletin is
the responsibility of each user or organisation, and should be considered in
accordance with your organisation's site policies and procedures. AusCERT
takes no responsibility for consequences which may arise from following or
acting on information or advice contained in this security bulletin.
===========================================================================
Australian Computer Emergency Response Team
The University of Queensland
Brisbane
Qld 4072
Internet Email: auscert@auscert.org.au
Facsimile: (07) 3365 7031
Telephone: (07) 3365 4417 (International: +61 7 3365 4417)
AusCERT personnel answer during Queensland business hours
which are GMT+10:00 (AEST).
On call after hours for member emergencies only.
===========================================================================
-----BEGIN PGP SIGNATURE-----
Comment: http://www.auscert.org.au/render.html?it=1967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=jjgu
-----END PGP SIGNATURE-----
|